      July 26, 2007 at 5:08 am #2882
      Avatar photo

      Hi all,

      In post tension literatures like Technical Report # 43 and PTI, the maximum tendon spacing in distributed direction is (8 x slab thickness).

      Here is a scenario:
      PT slab thickness = 250mm
      Spacing(Distributed direction) =1500mm
      max. tendon spacing (8xslab thk.) = 2000mm

      As per site condition, I have to move the whole tendon to the rightside by 300mm so that the spacing to the rightside will now be 1200mm and to the leftside is 1800mm (which is below max.spacing).

      My question is, am I right to say that I did not violate the design requirement of the pt slab by moving the tendon?

      Please clarify and confirm.

      lazar
      Participant
      Posts: 31
        July 29, 2007 at 4:50 pm #3139
        Avatar photo

        Hi Jone
        moving the tendon may effect the allowble stress, deflection or may cause changing in the normal steel in this area.
        even if the tendon spacing not more than allowble.
        so you have to tell your Designer to relocate the tendons and check the above thing before casting

        if the above thing within the limits , then you accept the tendons changing and cast your slab.
        and please if you have more details about this matter write any question and i will answer you

        John Mark B.
        Participant
        Posts: 25
          August 13, 2007 at 10:57 am #3146
          Avatar photo

          Hello there Mr. Yaser,

          Thank you so much for the explanation.
          Keep online from time to time because we need your technical expertise in this forum.

          cheers.

          -john mark-

          lazar
          Participant
          Posts: 31
            March 13, 2011 at 7:18 am #3336
            Avatar photo

            @yaser wrote:

            Hi Jone
            moving the tendon may effect the allowble stress, deflection or may cause changing in the normal steel in this area.
            even if the tendon spacing not more than allowble.
            so you have to tell your Designer to relocate the tendons and check the above thing before casting

            if the above thing within the limits , then you accept the tendons changing and cast your slab.
            and please if you have more details about this matter write any question and i will answer you

            i am a new guy to study the RAM can u give me some tips ?