      WHAT ARE POINTS SHOULD BE CHECKED IN A PT SLAB PROFILE INSPECTION ONLY HIGH OR LOW POINT IN COLUMNS OR ALL INDIVIDUAL CHAIR SUPPORTS, PLEASE SUGGEST APPORIATE WAY

      Administrator
      Keymaster
      Posts: 66
        May 21, 2009 at 8:50 am #3225
        Avatar photo

        I think consultant must check only high points and low points as those are marked in the approved by authority drawings.
        All the intermediate points are for support of the ducts purpose (maintaining the profile during concreting) and are figured only in the shop drawings which are not submitted for approval, neither to consultant nor to local authority.

        Ronaldo
        Participant
        Posts: 22
          May 24, 2009 at 11:51 am #3233
          Avatar photo

          in addttion to the above comment. high points and low points only are to be checked which are as per approved drawing…but then as for PROPER installation we have to maintain the parabolic profile of the tendon by means of proper placement of intermediate chairs.

          Decipher
          Participant
          Posts: 46
            May 25, 2009 at 5:53 pm #3235
            Avatar photo

            As i said before for consult u have approved drawings u should check by it
            this shop drawings i just need it to manage work in the site and between my labors

            IjazzGul
            Participant
            Posts: 20
              May 26, 2009 at 4:49 am #3239

              In a full perspective, the tendon layout must conform the drawings to ensure quality. So you need to check position along the tendon.

              You can simplify this though. Slab thickness is relatively small, so when high and low points are correct as per drawings, the other positions are theoretically also correct.

              In case of beam, you must at least check 1 other point: the inflection.