what is the allowable deviation in a single end stressed slab in percentage and also in double live end in pt slab that is + or – 10% what is the criteria or standard calculation.
the allowable deviation as per ACI is + or -7%.. if i'm not mistaken…plesase refer to ACI code…
As per AS (Australian standards) 3600-2001, A check shall be made for each tendon, on the correlation between measured extension & the calculated extension derived from the prestressing force,using the load elongation curves for the tendons & assumed friction values for the cable.Any disparity between the two figures greater than 10% of the calculated extension shall be investigated. means Variation between Actual elongation and theortical elongation must not be more than+ or – 10%.
as per BSI is +/- 6%
extracted part attached
@loida wrote:
the allowable deviation as per ACI is + or -7%.. if i'm not mistaken…plesase refer to ACI code…
Correct. you are not mistaken
as per ACI is 5% for pretensioned and 7% for post tensioned
the extracted part attached from ACI is: ACI 318M, chapter 18.18.1
All of the mentioned in this topic are correct, Australian Code +/-10 % or BSI +/-6 % or ACI +/-7 % all depend which code your authority follow.