      August 13, 2007 at 1:05 pm #2893
      Avatar photo

      Hi all,

      My question is,

      in BS8110-1:1997 Clause 8.6 “Positioning of Tendons and Sheaths”, it mentioned a tolerance of +/-5mm.

      Is this applicable to horizontal positioning or for vertical positioning only?

      John Mark B.
      Participant
      Posts: 25
        August 18, 2007 at 7:41 am #3148
        Avatar photo

        In my opinion that tolerance is for vertical positioning only (profiling). Post

        Tension Institute (PTI) recommneds horizontal tolerance of tendon placement. Please

        refer to the attached sheet.

        Refer also to TR 43 (other sheet).
        [file=../../e107_files/public/1187422863_7_FT38_tr43_tolerance.pdf]1187422863_7_FT38_tr43_tolerance.pdf[/file]

        [img:width=1700&height=2338]../../e107_files/public/1187422863_7_FT38_pti_reference.jpg[/img]

        Ronaldo
        Participant
        Posts: 22
          August 26, 2007 at 12:33 pm #3150
          Avatar photo

          you're asking about BS8110-1:1997………
          but for BS5400-7:1978 clause 5.6 for bridges. “the tendons,sheaths and duct formers shall be accurately located and maintained in position both vertically and horizontally as shown in the drawings. Unless otherwise shown on the drawings the tolerance in the location of the centre of the sheath or duct shall be -+5 mm.